When both directions are called at once

Each rung requires the other direction to be absent, so calling both makes each one block the other and neither runs.

Hone is a place to practise programming. This is one of its lessons, written out in full and free to read without an account.

What it is for

Refusing is the right answer. A motor commanded both ways at once is a fault upstream, not a decision to make.

How to think about it

Read the report 'it does nothing when I press both' as the interlock working, and say so. Time spent removing an interlock is time spent removing the thing protecting the gearbox.

Worked example

[Fwd] [/Rev] (M1)
[Rev] [/Fwd] (M2)
Forward alone, then both called. M1: 1 0

Your turn

Both directions called at once. How many motors run?

The trap

A program interlock is not enough on a reversing contactor. Contactors weld. The dangerous combination is also made impossible in the wiring.